Files
Nikolay MiroshnichenkoandClaude Opus 5 a3f436fc74 generate_ha: one climate entity per physical device, fail closed when devices cannot be told apart
Found on a real 1312-GA house: a room with floor heating, a convector and an AC unit became
ONE climate (convector setpoint, AC controller mode, AC fan speed as the valve). Room 1.09
matched 2.09 and a central "09." GA, "Kids room 1" took "Kids room 2 temperature", and valves
came from light brightness and blind position statuses. The zone was the room alone: device
words were stripped as qualifiers, "А/С" vanishes in the tokenizer, the floor digit of "1.09"
is dropped.

Now a climate is assembled per room AND device type (floor, wall, radiator/convector, fan
coil, AC; RU/EN/DE words, removed from the zone as whole words):
- room code "N.NN" only at the start of a name, and it must match on both sides;
- standalone numbers of the anchor must be in a device member; a shared room sensor's
  numbers must be among the anchor's; digits in dotted codes and values do not count;
- an untyped GA is shared room data: any role if the room has one device, otherwise only
  the current temperature, which several devices may reuse; with a room code the room's
  untyped sensor qualifies even without the device's extra words;
- a word that sets another device of the room apart keeps its GAs away;
- control roles must be unambiguous: more than one candidate -> review climate_ambiguous;
- two mode GAs that cannot be told apart -> review climate_duplicate_anchor, not dropped;
- only 20.102 / 20.105 anchor; valve needs a valve word; AC never gets a valve;
- stable address order, so results never depend on parse order.

Two gates. Own audit on seven real projects, every changed entity inspected: no control GA
used by two climates, no address lost; house 16 -> 33 climates (one per device), manual
review 33 -> 12; flat 7 -> 9; HDL 3 -> 5; demo 6 -> 13; villa 23 -> 21 with the 3 it cannot
disambiguate sent to review instead of guessed. LLM council (three models + devil's
advocate, sanitised packet): accept with hardening; its P0s (same-type devices, silent
first pick) and P1s (mid-name codes, dotted digits, non-102/105 anchors, generic valve
words) are all in this commit, with tests E and F covering its failure catalogue.
Out of scope, recorded: identically named rooms of different flats without room codes, and
lexical identity in general -> device-channel identity ("lever 0").

Also works around a mypy 2.3.1 parse error on a comment right after a compound if.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-09-16 19:20:49 +02:00
..
2026-09-14 00:18:27 +02:00