mirror of
https://github.com/NickoScope/nickol-knx-mcp.git
synced 2026-09-29 19:31:12 +02:00
generate_ha: one climate entity per physical device, fail closed when devices cannot be told apart
Found on a real 1312-GA house: a room with floor heating, a convector and an AC unit became
ONE climate (convector setpoint, AC controller mode, AC fan speed as the valve). Room 1.09
matched 2.09 and a central "09." GA, "Kids room 1" took "Kids room 2 temperature", and valves
came from light brightness and blind position statuses. The zone was the room alone: device
words were stripped as qualifiers, "А/С" vanishes in the tokenizer, the floor digit of "1.09"
is dropped.
Now a climate is assembled per room AND device type (floor, wall, radiator/convector, fan
coil, AC; RU/EN/DE words, removed from the zone as whole words):
- room code "N.NN" only at the start of a name, and it must match on both sides;
- standalone numbers of the anchor must be in a device member; a shared room sensor's
numbers must be among the anchor's; digits in dotted codes and values do not count;
- an untyped GA is shared room data: any role if the room has one device, otherwise only
the current temperature, which several devices may reuse; with a room code the room's
untyped sensor qualifies even without the device's extra words;
- a word that sets another device of the room apart keeps its GAs away;
- control roles must be unambiguous: more than one candidate -> review climate_ambiguous;
- two mode GAs that cannot be told apart -> review climate_duplicate_anchor, not dropped;
- only 20.102 / 20.105 anchor; valve needs a valve word; AC never gets a valve;
- stable address order, so results never depend on parse order.
Two gates. Own audit on seven real projects, every changed entity inspected: no control GA
used by two climates, no address lost; house 16 -> 33 climates (one per device), manual
review 33 -> 12; flat 7 -> 9; HDL 3 -> 5; demo 6 -> 13; villa 23 -> 21 with the 3 it cannot
disambiguate sent to review instead of guessed. LLM council (three models + devil's
advocate, sanitised packet): accept with hardening; its P0s (same-type devices, silent
first pick) and P1s (mid-name codes, dotted digits, non-102/105 anchors, generic valve
words) are all in this commit, with tests E and F covering its failure catalogue.
Out of scope, recorded: identically named rooms of different flats without room codes, and
lexical identity in general -> device-channel identity ("lever 0").
Also works around a mypy 2.3.1 parse error on a comment right after a compound if.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
This commit is contained in:
co-authored by
Claude Opus 5
parent
76249469bb
commit
a3f436fc74
@@ -8,6 +8,25 @@ and this project adheres to [Semantic Versioning](https://semver.org/spec/v2.0.0
|
||||
|
||||
### Fixed
|
||||
|
||||
- **Climate entities no longer merge different devices of one room.** A room with floor heating, a
|
||||
convector or radiator and an AC unit used to become a single Home Assistant climate: the convector's
|
||||
setpoint, the AC's controller mode and the AC fan speed as the "valve". Valves were also taken from
|
||||
unrelated 5.x statuses (light brightness, blind position), room "1.09" matched "2.09", and "Kids
|
||||
room 1" took "Kids room 2 temperature". A climate is now assembled per room **and** device type
|
||||
(floor / wall / radiator-convector / AC, detected in RU/EN/DE names): the room code ("1.09") and the
|
||||
numbers in the anchor name must match, a shared untyped room sensor may serve every device in the
|
||||
room as current temperature but never as a device's setpoint or mode, a valve needs a valve word and
|
||||
an AC never gets one. Hardened after an LLM-council review: a word that sets another device of the
|
||||
room apart ("shower", "hall") keeps its GAs away; if a control role still has more than one candidate
|
||||
the device goes to review as `climate_ambiguous` instead of taking the first; two mode GAs that cannot
|
||||
be told apart go to review as `climate_duplicate_anchor` instead of being dropped silently; room codes
|
||||
only count at the start of a name ("21.5 °C", "16.10", "ДД 34.1" are not rooms); digits inside dotted
|
||||
codes are not room numbers; only 20.102 and 20.105 start a climate; fan coils and VRV/VRF are their
|
||||
own device types; valve words narrowed to valve / клапан / Stellwert. On seven real projects: no
|
||||
control GA used by two climates, no address lost. A 1312-GA house goes from 16 climates (several
|
||||
wrong) to 33 (one per device), manual climate review 33 -> 12; a 3646-GA villa keeps 21 of 23 and
|
||||
sends the 3 it cannot disambiguate (three thermostats in one corridor, two identical AC mode GAs) to
|
||||
review instead of guessing.
|
||||
- **Home Assistant lights without `address` are no longer generated.** A 5.001 lighting GA with no
|
||||
on/off GA in its zone used to become a light with only `brightness_address`, which Home Assistant
|
||||
rejects (`address` is required on a KNX light). On six real projects 51 such lights were generated,
|
||||
|
||||
Reference in New Issue