feat: sub-DPT linter + KNX Secure posture (v0.4.0)
A1 — sub-DPT sanity linter: when a GA name implies a specific DPT sub-type (temperature->9.001, power->14.056, brightness/position->5.001), flag a wrong sub or wrong main. Multilingual, conservative; surfaced as the subdpt_suspect finding via check_dpt / analyze_all. A4 — KNX Data Secure posture: secure_posture() + new check_secure MCP tool. Report-only summary (secured vs plaintext counts, mixed secure/plaintext middle groups, keyring handover checklist). Reads only the per-GA Security flag; no key material touched. Handover pack section 5 rewritten to this posture section. Version bump to 0.4.0; CHANGELOG updated. Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
This commit is contained in:
co-authored by
Claude Opus 4.8
parent
b16492eb68
commit
44e1ae3aa7
+32
-1
@@ -450,7 +450,7 @@ _hmd = _hp["markdown"]
|
||||
# all seven sections present
|
||||
for _sec in ("# KNX Handover Pack", "## 1. Topology", "## 2. Equipment inventory",
|
||||
"## 3. Group-address map by domain", "## 4. Command / status coverage",
|
||||
"## 5. KNX Secure scope", "## 6. QA state at handover", "## 7. Pack contents"):
|
||||
"## 5. KNX Secure posture", "## 6. QA state at handover", "## 7. Pack contents"):
|
||||
assert _sec in _hmd, f"handover missing section: {_sec}"
|
||||
# equipment inventory picked up the synthetic MDT device + its order number
|
||||
assert "MDT" in _hmd and "AKK-0416.03" in _hmd, "device inventory not rendered"
|
||||
@@ -487,3 +487,34 @@ _miss=decompose_device("totally-unknown-xyz")
|
||||
assert _miss["matched"] is False
|
||||
assert len(list_recipes())>=10
|
||||
print("OK: decompose_device — dimmer 3.007+5.001, shutter 1.008, panel=0, unknown handled")
|
||||
|
||||
# --------------------------------------------------------------------------- #
|
||||
# Regression (v0.4.0): A1 sub-DPT linter + A4 KNX Secure posture.
|
||||
# --------------------------------------------------------------------------- #
|
||||
print("\n=== REGRESSION: A1 sub-DPT linter + A4 secure posture ===")
|
||||
from nickol_knx_mcp.analyze import secure_posture
|
||||
_rawA1 = {"group_addresses": {
|
||||
"5/0/0": ga("5/0/0", "Гостиная - Температура воздуха", 9, 4), # temp but 9.004(lux) -> suspect
|
||||
"5/0/1": ga("5/0/1", "Спальня - Температура", 9, 1), # correct -> ok
|
||||
"1/0/0": ga("1/0/0", "Kitchen brightness value", 5, 10), # brightness but 5.010 -> suspect
|
||||
"1/0/1": ga("1/0/1", "Hall brightness value", 5, 1), # correct
|
||||
"2/0/0": ga("2/0/0", "CO2 living room", 5, 1), # co2 (strong) wrong main -> suspect
|
||||
}}
|
||||
_sd = {(f["code"], f["address"]) for f in detect_dpt_issues(build_loaded_from_raw(_rawA1, "mem"))}
|
||||
assert ("subdpt_suspect", "5/0/0") in _sd, "temp 9.004 not caught"
|
||||
assert ("subdpt_suspect", "1/0/0") in _sd, "brightness 5.010 not caught"
|
||||
assert ("subdpt_suspect", "2/0/0") in _sd, "co2 wrong-main not caught"
|
||||
assert ("subdpt_suspect", "5/0/1") not in _sd and ("subdpt_suspect", "1/0/1") not in _sd, "false positive on correct DPT"
|
||||
print("OK: sub-DPT linter — wrong sub + wrong main caught, correct DPTs clean")
|
||||
|
||||
_rawS = {"group_addresses": {
|
||||
"1/0/0": ga("1/0/0", "Kitchen switch", 1, 1, secure=True),
|
||||
"1/0/1": ga("1/0/1", "Kitchen switch status", 1, 11, secure=False), # same middle -> mixed
|
||||
"2/0/0": ga("2/0/0", "Hall switch", 1, 1, secure=True),
|
||||
}}
|
||||
_sp = secure_posture(build_loaded_from_raw(_rawS, "mem"))
|
||||
assert _sp["secured"] == 2 and _sp["plaintext"] == 1, _sp
|
||||
assert _sp["keyring_required"] is True
|
||||
assert len(_sp["mixed_middle_groups"]) >= 1, "mixed secure/plaintext middle not flagged"
|
||||
assert any("keyring" in s.lower() for s in _sp["checklist"]), "no keyring step"
|
||||
print("OK: secure posture — counts, mixed-middle flag, keyring checklist")
|
||||
|
||||